How to work out the transformer size you need
Load calculation in plain steps, from connected load in kW to transformer rating in kVA.
Transformers are rated in kVA, not kW. Choosing the size is a four-step sum.
- Add up the connected load. List every lift, pump, air conditioner, light and socket circuit with its kW rating and add them together.
- Apply a demand factor. Not everything runs at once. The building code says to apply a load factor of at least 80% when sizing a substation.
- Convert kW to kVA. Divide by the power factor. Without correction a typical building runs near 0.8.
- Allow for growth. Add 15 to 25% so the transformer is not at its limit on day one.
Example: 220 kW connected × 0.8 demand = 176 kW. 176 ÷ 0.8 power factor = 220 kVA. Add 20% growth = 264 kVA. The next standard size up is 315 kVA.
Standard distribution transformer sizes are 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600 and 2000 kVA. Use the calculator on the guides page for your own numbers, then let our engineer confirm it on site: motor starting currents and lift loads can push the answer up a size.